Speakman SE-565 Bedienerhandbuch

Stöbern Sie online oder laden Sie Bedienerhandbuch nach Sanitärkeramik Speakman SE-565 herunter. Speakman SE-565 Instructions / Assembly Benutzerhandbuch

  • Herunterladen
  • Zu meinen Handbüchern hinzufügen
  • Drucken
  • Seite
    / 2
  • Inhaltsverzeichnis
  • LESEZEICHEN
  • Bewertet. / 5. Basierend auf Kundenbewertungen
Seitenansicht 0
SPEAKMAN COMPANY
SE-565 Installation, Maintenance & Operation Instructions
EYESAVER® EYEWASH
DESCRIPTION
Deck mounted emergency eyewash. Supplied with stainless steel bowl, stay-open full flow ball valve; activated by
stainless steel trigger bar; adjustable volume regulator, aerated spray outlets with individual adjustments for
maximum performance, and mounted on counter tops up to 2” thick.
SPECIFICATIONS
BOWL: 300 Series Stainless Steel.
SPRAY HEADS: (2) Brass, Chrome-Plated, Aerated.
VALVE: 1/2” NPT Female Brass, Chrome-Plated.
ACTIVATOR: Stainless Steel Trigger Bar.
INLET: 1/2” NPT Female.
SHIPPING WEIGHT: 7.1 lbs.
EMERGENCY SIGN: 7-7/8” x 7-7/8” Plastic Wall Sign.
OPTIONS
AL1 (Air Horn Alarm) VPL (Vapor Proof Light) SSBV2 (1/2” Stainless Steel Valve)
AL2 (Electrical Alarm) PT (P-Trap)
AL3 (Electrical Alarm) ILS (In-Line Strainer)
AL2-C1D2 (Electrical Alarm / Haz.
Area)
SGN4
(Eye Wash Floor Sign)
AL3-C1D2 (Electrical Alarm / Haz.
Area)
FPV
(Anti-Freeze Protection Valve)
FLW (Flow Switch) SPV (Anti-Scald Protection Valve)
INSTALLATION
Use cutting/drilling instruction template (supplied) to cut and drill holes in desired location on countertop. Once
bowl is mounted securely to countertop using mounting hardware supplied, complete assembly of ball valve and
push handle. Review drawing (as shown on other side) to assure proper installation. Be sure to apply a bead of
waterproof caulk along edge of bowl and countertop to prevent water draining under countertop. Connect a water
supply to the unit (use pipe sealant on all joints) that is a 1/2” minimum uninterrupted source of potable water.
Failure to use potable water can result in emergency units producing impure or contaminated water causing
possible further injury. The drain tailpiece or waste should be connected to an adequate drain in compliance with
local plumbing codes. This unit is supplied with a volume control that can control the amount of water delivered,
even at higher pressures. This should be set after unit is completely installed so that streams from spray outlets
converge in the middle of the eyewash bowl..
OPERATION
The eyewash is activated by pushing the trigger bar back 90°. Once the unit is activated, water will discharge from
the spray outlets until the trigger bar is manually pulled back to the off position.
TESTING PROGRAM
The American National Standards Institute (ANSI) states that all safety emergency equipment shall be activated on
a weekly basis to flush the line and verify proper operation. Speakman Company furnishes a testing record tag
(91-0635) with each unit. On this tag the date of inspection and the inspectors initials should be noted.
Seitenansicht 0
1 2

Inhaltsverzeichnis

Seite 1 - SPEAKMAN COMPANY

SPEAKMAN COMPANYSE-565 Installation, Maintenance & Operation Instructions EYESAVER® EYEWASH DESCRIPTION Deck mounted emergency eyewash. Sup

Seite 2

MAINTENANCE 04/02 92-1448 Rev-5 The valve and the eyewash are the only portions of the unit that may require maintenance. Should you need parts to

Kommentare zu diesen Handbüchern

Keine Kommentare